Water Quality Analysis: Foundation for Cleaning
Power plants typically use surface water, groundwater, or reclaimed water - each with unique characteristics:
- Surface water: High in suspended solids, organics, and microbes.
- Groundwater: Stable but high in hardness, prone to scaling.
- Reclaimed water: Rich in ammonia nitrogen and biodegradable matter.
Key parameters include turbidity, SDI, pH, conductivity, hardness, and microbial count. For optimal performance, turbidity < 1 NTU and SDI < 5 are recommended.
Common Membrane Fouling Types & Cleaning Methods
1.Inorganic Scaling
Caused by calcium, magnesium, and iron ions forming CaCO₃ or CaSO₄.
→ Use acidic cleaners (citric acid or dilute HCl), maintain pH 2–4 for 1–2 hours.
2.Organic Fouling
Results from proteins, oils, and polysaccharides.
→ Use alkaline cleaners (NaOH) with surfactants at pH 10–12, 15°C for 2–3 hours.
3.Biofouling
Formed by microbial growth on membrane surfaces.
→ Disinfect with 50–200 mg/L NaOCl, followed by biological cleaners to remove residues.
Determining the Right Cleaning Time
Cleaning should be performed when:
- Permeate flow drops by 10–15%;
- Salt rejection decreases by over 5%;
- Pressure differential increases by 15–20%;
- SDI or turbidity shows a sharp rise.
Case Study
A power plant using surface water experienced reduced output and high pressure drop after months of operation. Combined inorganic and organic fouling was diagnosed.
Cleaning method: Acid cleaning with citric acid followed by alkaline cleaning with NaOH and surfactant mixture.
Results:
| Parameter | Before | After |
|---|---|---|
| Permeate flow (m³/h) | 80 | 95 |
| Salt rejection (%) | 96 | 98 |
| Pressure drop (MPa) | 0.30 | 0.15 |
| Conductivity (μS/cm) | 50 | 30 |
Performance fully recovered, demonstrating the effectiveness of targeted cleaning.
Routine Maintenance Recommendations
Optimize pretreatment: Replace cartridge filters, add coagulants and biocides properly.
Control operation parameters: Maintain stable pressure and flow; flush membranes regularly.
Storage protection: Use 1–2% sodium bisulfite solution during shutdowns to prevent microbial growth.